Attention: Due to the large number of products from our company, the pictures cannot match each other. Please contact me to confirm the actual product!
IC694CHS392 is a 10-slot serial expansion backplane in the GE Fanuc PACSystems RX3i series. It is used to expand the number of I/O modules and support the distributed architecture of control systems. Here are its detailed specifications:
- Model: IC694CHS392
- Brand: GE Fanuc
- Series: RX3i PACSystem
- Function: Serves as a serial expansion backplane to connect I/O modules with the main controller, supporting distributed I/O configurations.
Parameter |
Details |
Number of Slots |
10 slots (The first slot on the left must be occupied by a power module; the rest are for I/O modules or special-function modules). |
Communication Protocol |
Supports GE Fanuc’s SNP (Serial Network Protocol) for communication with the main controller. |
Expansion Distance |
Maximum expansion distance of 15 meters (50 feet); multiple expansion backplanes can be connected via a daisy-chain. |
Power Requirements |
– 5VDC (provided by a power module such as IC694PWR331) – Backplane’s own power consumption is approximately 150mA. |
Mechanical Specifications |
– Dimensions: 13.0cm (length) × 44.3cm (width) × 14.2cm (height) – Weight: Approximately 1.8kg. |
Operating Environment |
– Temperature: 0°C to 60°C (non-condensing) – Humidity: 5% to 95% (non-condensing). |
Protection Class |
IP20 (must be installed in a control cabinet). |

-
Distributed I/O Expansion
Connects the main controller to extended I/O modules via a serial bus, supporting remote installation and adapting to large-scale control systems.
-
Modular Design
Can flexibly configure different types of I/O modules (digital, analog, special-function modules) to meet diverse needs.
-
Hot-Swap Support
Some modules support hot-swapping (specific module models need to be confirmed), reducing system downtime.
-
Redundancy Capability
Compatible with dual-CPU redundant configurations (when used with the RX3i redundant system), improving system reliability.
-
Termination Management
A termination resistor (such as IC693ACC307) must be installed at the end of the backplane to prevent signal reflection and ensure stable communication.

- Module Installation: The leftmost slot must be occupied by a serial power module (e.g., IC694PWR331/330/321). Unused slots require filler panels to prevent dust and ensure heat dissipation.
- Wiring Requirements: Use shielded cables for serial communication to reduce electromagnetic interference (EMI).
- Power Safety: Power off before installing/uninstalling modules (hot-swap is not supported for the backplane itself).
Widely used in industrial automation systems requiring large-scale I/O expansion, such as:
- Production line control (automotive, electronics manufacturing)
- Process control (chemical, pharmaceutical, water treatment)
- Distributed monitoring systems (power, metallurgy)

Related products:
GE |
IC200GBI001 |
GE |
IC3645LXCD1 |
GE |
IC660BBD025 |
GE |
IC660EBD020 |
GE |
IC660ELB912G |
GE |
IC660ELD100A |
GE |
IC660TSA100 |
GE |
IC670CBL001 |
GE |
IC670CHS001 |
GE |
IC670CHS002 |
[Disclaimer]
Our company sells new products and discontinued products, and purchases such special products through independent channels. Guizhou Yuanmiao Automation Equipment Co., Ltd. is not an authorized distributor, distributor or representative of the featured products of this website. All product names/product images, trademarks, brands and microlabels used on this website are the property of their respective owners. Product descriptions, descriptions or sales with these name images, trademarks, brands and logos are for identification purposes only and do not represent any association or authorization with any right holders.