Attention: Due to the large number of products from our company, the pictures cannot match each other. Please contact me to confirm the actual product!

-
Product Overview:
- Product Type: Motor management relay.
- Function: It optimizes motor performance and reduces downtime through real-time monitoring, event reporting, and waveform capture, and can provide protection and monitoring for motors.
- Application Scenarios: Suitable for industrial motor – related scenarios and can operate reliably in harsh industrial environments.
-
Technical Parameters:
- Control Power Supply: 50 – 300VDC / 40 – 265VAC.
- Phase Current Input: 1A and 5A secondary.
- Digital Inputs: 6 optically isolated digital / switch inputs.
- Communication Interfaces: Equipped with RS232 port and RS485 port.
- Event Recording: Can record the last 512 events.
- Waveform Capture: 3 buffers, including 16 cycles of all current and voltage channels.
- Dimensions and Weight: Approximately 11.5 inches in height × 5.5 inches in width × 8.5 inches in length, and weighs about 10 pounds.
- Working Environment: The operating temperature range is – 40℃ to + 60℃, the humidity should be kept below 95% without condensation, and the maximum altitude is 2000 meters.

-
Functional Features:
- Protection Functions: It has protection functions such as overcurrent, phase loss, locked rotor, reverse rotation, current imbalance, etc., and can also issue predictive alarms.
- Metering Functions: Including event reporting, waveform capture, and start – up data recording, etc. It can provide key insights into system performance and warn of impending faults.
- Other Functions: Settings such as motor inrush current, cooling rate, and acceleration time can be adjusted to allow users to optimize system performance.

-
Model Interpretation:
- “369” indicates a basic relay unit without RTD.
- “HI” indicates that the relay has a 50 – 300VDC / 40 – 265VAC control power supply.
- “R” indicates 12 built – in RTD inputs.
- “M” indicates that the relay is accompanied by an optional metering package.
- The first “0” indicates that there is no optional optical fiber port.
- “D” has not been clearly interpreted in existing data and is presumably related to specific functions or configurations.
- The second “0” indicates that there is no optional special protocol interface.
- “E” indicates that the relay includes an optional Modbus / TCP protocol interface.

Related products:
[Disclaimer]
Our company sells new products and discontinued products, and purchases such special products through independent channels. Guizhou Yuanmiao Automation Equipment Co., Ltd. is not an authorized distributor, distributor or representative of the featured products of this website. All product names/product images, trademarks, brands and microlabels used on this website are the property of their respective owners. Product descriptions, descriptions or sales with these name images, trademarks, brands and logos are for identification purposes only and do not represent any association or authorization with any right holders.